Monday to Friday, 8:00 a.m. to 4:00 p.m. · Saturday, 8:00 a.m. to 1:00 p.m.

Cybersecurity

CISA warns of attacks on industrial refrigeration systems

Cold room at a food plant with metal racks and an evaporator on the ceiling

CISA and the FBI warn that attackers target the temperature controllers of cold rooms and commercial refrigerators, and France has confirmed one such attack on more than 700 supermarkets. What to check and how to protect them.

On November 5, 2026, the US Cybersecurity and Infrastructure Security Agency (CISA), the FBI and the US Departments of Health and Human Services, Agriculture and Transportation published a joint alert: attackers around the world are targeting industrial refrigeration and cold chain monitoring systems. Their goal is to change settings remotely and force the equipment into continuous heating and defrost cycles, which can ruin an entire inventory.

What is happening

According to the alert, the attackers go after electronic temperature controllers and commercial refrigeration controllers in grocery stores and cold storage facilities. They exploit unpatched or internet-accessible devices in three ways: bypassing authentication (the username and password login), injecting code or abusing weak configurations.

If they succeed, they can change the temperature, which shortens the equipment's service life, creates a fire hazard, causes inventory loss and can harm consumers if poorly stored products are sold. They can also leave the business unable to see the real temperatures.

Who should check their equipment

These systems are used to monitor temperatures remotely, log them continuously, manage defrost cycles and save energy, including in refrigerated transport. The alert names the healthcare, chemical, food and agriculture, and transportation sectors. In practice it applies to any business with cold rooms or refrigerators monitored over the internet, such as grocery stores, pharmacies, laboratories, food plants or restaurants.

What to do

  1. Take an inventory of your temperature controllers and monitoring software, and ask your vendor whether any of them can be reached from the internet.
  2. Take control panels off the internet. If you need remote access, route it through an up-to-date firewall or VPN.
  3. Place these devices on their own virtual network (VLAN), separate from the company's computers and servers.
  4. Change default passwords, use strong passwords and turn on two-factor authentication wherever possible.
  5. Update the firmware (the device's internal software) and plan to replace controllers the manufacturer no longer supports.
  6. Allow changes only from authorized devices and IP addresses, and set safe temperature ranges with alerts when readings fall outside them.
  7. Keep backups offsite and offline, test them and review logs for unexpected activity.

November 10 update: France blames Iran for an attack on 700 supermarkets

On November 9, France's Ministry for Europe and Foreign Affairs reported that, on the night of October 11 to 12, a cyberattack campaign hit supermarket refrigeration controllers at more than 700 sites belonging to large retail chains in the country. According to the ministry, it caused considerable material damage, several fires and food losses estimated at tens of millions of euros. France attributes it to Shahid Kaveh, a unit of Iran's Revolutionary Guard. The technical report released that day by CERT-FR, the incident response team of the French cybersecurity agency (ANSSI), states that the attackers set the defrost parameters to high temperatures, causing heavy merchandise losses and at least 15 fires. This is the kind of damage the CISA alert describes: if your cold rooms or refrigerators have connected controllers, apply the steps above now.

November 16 update: 14 flaws in Copeland XWEB EVO supervisors

On November 13, security firm VulnCheck disclosed 14 vulnerabilities in XWEB EVO, the Dixell refrigeration supervisor now sold by Copeland, which is installed, for example, in supermarket back offices to control all of their refrigeration equipment. According to VulnCheck, every one of them leads to root (full control of the device), and its decoy sensors have already recorded real attempts to exploit two of them. CVE-2026-124010, scored 9.8 out of 10, runs commands as root with a single web request and no password on versions before 5.6.2. CVE-2026-124014, scored 9.1, lets an unauthenticated attacker change the system configuration and affects versions 4.3.0 through 5.8.8, the latest. In a Shodan search, VulnCheck found about 1,663 XWEB EVO units reachable from the internet.

There will be no patches: Copeland ended software support for the XWEB EVO family on March 16, 2026. It recommends identifying every installation, planning the move to XWEB PRO models and, in the meantime, isolating the devices on their own network, restricting access and monitoring them closely. If you have an XWEB EVO, steps 2, 3 and 5 of “What to do” are now urgent: take it off the internet and plan its replacement.

November 17 update: six unpatched flaws in the Danfoss AK-SM 800A

Dutch firm Midnight Blue reported in November that it found six vulnerabilities in the AK-SM 800A, a Danfoss controller for refrigeration systems, in less than an hour of manual review. According to its analysis, all of them allow remote code execution without logging in and affect every version up to 5.3.2. They could give full control of the device, persistent access, possibly even after a reset, or leave it unusable. They have no CVE or patch yet, and the firm is withholding technical details while it coordinates disclosure with Danfoss. Midnight Blue notes that the attacks that began in France on October 11 hit internet-exposed Danfoss and Copeland controllers across Europe.

On November 13, Germany's Federal Office for Information Security (BSI) confirmed that versions up to at least 5.3.2 are affected and that no active exploitation is known. It corrected its first statement: it cannot rule out that version 5.4.0, released in November, is also affected. Both advise against connecting these devices directly to the internet and, if remote maintenance is needed, using at least a VPN; Midnight Blue recommends prioritizing removing that exposure over installing patches one by one. If you have a Danfoss AK-SM 800A, step 2 of “What to do” is urgent.

How we help you

With network design with separate segments we isolate refrigeration and monitoring equipment from the rest of your network and set up remote access over VPN. With management of your technology infrastructure we keep your device inventory and updates current. Tell us which devices you have and we will check whether they are exposed.

Sources

Source: CISA

Keep reading

White router with four antennas lit in blue and pink

Cybersecurity

GL.iNet: attackers hit routers and KVMs through its cloud

GL.iNet confirmed that an attacker abused a flaw in its cloud remote management service to install malware on some of its routers and KVM devices. How to check your devices and which firmware to install.

Person taking a sheet out of a printer in an office with large windows

Cybersecurity

Ghostscript: a crafted file can take over the server

Research firm pwn.ai showed how a crafted file exploits Ghostscript flaw CVE-2026-125396 to run commands on servers with WordPress, Roundcube or shared printers. A fix is available.

Antique brass keys laid out in rows on a dark surface

Cybersecurity

GnuPG fixes a critical flaw in GPGME and Gpg4win

GnuPG released GPGME 2.3.1 and Gpg4win 5.1.2 to fix CVE-2026-129975, a critical flaw: a crafted OpenPGP key can pull data out of programs and might allow code execution. What to update.

Chat with Pronetsys on WhatsApp